10.1007/s40095-020-00376-8

Study on summer thermal performance of a solar ventilated window integrated with thermoelectric air-cooling system

  1. Department of Mechanical Engineering, Shiraz University of Technology, Shiraz, IR

Published in Issue 2021-02-11

How to Cite

Khalvati, F., Omidvar, A., & Hadianfard, F. (2021). Study on summer thermal performance of a solar ventilated window integrated with thermoelectric air-cooling system. International Journal of Energy and Environmental Engineering, 12(3 (September 2021). https://doi.org/10.1007/s40095-020-00376-8

Abstract

Abstract In this paper, a thermoelectric air-cooling system was used to cool down the airflow window glazing surfaces during summer in hot climates by which cooling load of the indoors and occupant’s thermal discomfort near the window reduce. The performance of the proposed system was modeled analytically, in which the models used were validated by the literature experiment results. To determine the thermoelectric system specifications, the three features of the system including the time working interval, the number of modules, and the degree of air temperature attenuation were investigated. The results show that using the thermoelectric air cooling system for the limited time interval within hours of peak cooling load can significantly reduce the energy consumption, while using the system for a longer time interval not only cannot decrease the energy consumption but also may increase. Besides, the results reveal that the thermoelectric system with 15 modules is required to be energy efficient. On the other hand, an increase in the number of modules more than 20 has no considerable effect on energy saving. Furthermore, the percentage of energy saving is 6.5% for 5 °C air cooling and reached a maximum of 7.1% for 7 °C air cooling, while for 10 °C, this value is zero. The mean reduction of the maximum interior glazing surface temperature is 5.9 and 7.4 °C for air cooling degrees of 5 and 10 °C.

Keywords

  • Airflow window,
  • Solar ventilated,
  • Thermoelectric cooling,
  • Zonal model,
  • Energy saving

References

  1. Wright, J.L.: Effective U-values and shading coefficients of preheat/supply air glazing systems. In: Proceedings of Solar Energy Society of Canada, Winnipeg, Canada, pp. 219–224 (1986)
  2. Gosselin and Chen (2008) A dual airflow window for indoor air quality improvement and energy conservation in buildings (pp. 359-372) https://doi.org/10.1080/10789669.2008.10391014
  3. Chow et al. (2006) Use of ventilated solar screen window in warm climate (pp. 1910-1918) https://doi.org/10.1016/j.applthermaleng.2006.01.026
  4. Zhang et al. (2016) Modeling and thermal performance evaluation of a switchable triple glazing exhaust air window (pp. 8-17) https://doi.org/10.1016/j.applthermaleng.2015.09.080
  5. Kim et al. (2006) Thermal performance of the exhausting and the semi-exhausting triple-glazed airflow windows (pp. 177-190) https://doi.org/10.1002/er.1149
  6. Du et al. (2020) Study and analysis of air flow characteristics in Trombe wall (pp. 234-241) https://doi.org/10.1016/j.renene.2020.08.040
  7. Bellos et al. (2016) An innovative Trombe wall as a passive heating system for a building in Athens—A comparison with the conventional Trombe wall and the insulated wall (pp. 754-769) https://doi.org/10.1016/j.enbuild.2016.10.035
  8. Wang et al. (2020) Classification, experimental assessment, modeling methods and evaluation metrics of Trombe walls https://doi.org/10.1016/j.rser.2020.109772
  9. Chow et al. (2009) A comparative study of PV glazing performance in warm climate (pp. 32-40) https://doi.org/10.1177/1420326X08100323
  10. Hweij et al. (2017) Evaporatively-cooled window driven by solar chimney to improve energy efficiency and thermal comfort in dry desert climate (pp. 755-761) https://doi.org/10.1016/j.enbuild.2017.01.071
  11. Ghadimi et al. (2012) Analysis of free and forced convection in airflow windows using numerical simulation of heat transfer https://doi.org/10.1186/2251-6832-3-14
  12. Wei et al. (2010) Optimal design for a dual-airflow window for different climate regions in China (pp. 2200-2205) https://doi.org/10.1016/j.enbuild.2010.07.016
  13. Scaff and Gosselin (2014) Summer performance of ventilated windows with absorbing or smart glazings (pp. 2-13) https://doi.org/10.1016/j.solener.2013.08.025
  14. Lago et al. (2019) Ventilated double glass window with reflective film: modeling and assessment of performance (pp. 72-88) https://doi.org/10.1016/j.solener.2019.04.047
  15. Hu and Heiselberg (2018) A new ventilated window with PCM heat exchanger—Performance analysis and design optimization (pp. 185-194) https://doi.org/10.1016/j.enbuild.2018.03.060
  16. Hu et al. (2020) Ventilation cooling/heating performance of a PCM enhanced ventilated window: an experimental study https://doi.org/10.1016/j.enbuild.2020.109903
  17. Hu et al. (2020) Performance and control strategy development of a PCM enhanced ventilated window system by a combined experimental and numerical study (pp. 134-152) https://doi.org/10.1016/j.renene.2020.03.137
  18. Wang et al. (2021) The study of a double-skin ventilated window integrated with CdTe cells in a rural building https://doi.org/10.1016/j.energy.2020.119043
  19. Al Touma et al. (2016) Solar chimney integrated with passive evaporative cooler applied on glazing surfaces (pp. 169-179) https://doi.org/10.1016/j.energy.2016.09.020
  20. Xu and Dessel (2008) Evaluation of a prototype active building envelope window-system (pp. 168-174) https://doi.org/10.1016/j.enbuild.2007.02.027
  21. Arenas-Alonso, A., Palacios, R., Rodríguez-Pecharromán, R., Pagola, F.L.: Full-size prototype of active thermal windows based on thermoelectricity. In: 6th European Conference on Thermoelectrics, Paris, France (2008)
  22. Zhao and Tan (2014) A review of thermoelectric cooling: Materials, modeling and applications (pp. 15-24) https://doi.org/10.1016/j.applthermaleng.2014.01.074
  23. Fraisse et al. (2013) Comparison of different modeling approaches for thermoelectric elements (pp. 351-356) https://doi.org/10.1016/j.enconman.2012.08.022
  24. Pierres et al. (2008) Coupling of thermoelectric modules with a photovoltaic panel for air pre-heating and pre-cooling application; an annual simulation (pp. 1316-1328) https://doi.org/10.1002/er.1439
  25. Han, H.S., Kim, S.Y., Ji. T.H. Jee, Y.J., Lee, D., Jang, K.S., Oh, D.H.: Heat sink design for a thermoelectric cooling system. 11th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems. IEEE, 1222–1230 (2008)
  26. Hadianfard et al. (2018) Study on the effect of heat sinks layout and air flow pattern through the fins on thermal performance of thermoelectric air-handling units (pp. 265-276)
  27. Balocco (2004) A non-dimensional analysis of a ventilated double facade energy performance (pp. 35-40) https://doi.org/10.1016/S0378-7788(03)00086-0
  28. Gratia and De Herde (2004) Natural ventilation in a double-skin facade (pp. 137-146) https://doi.org/10.1016/j.enbuild.2003.10.008
  29. Stec and van Paassen (2005) Symbiosis of the double skin façade with the HVAC system (pp. 461-469) https://doi.org/10.1016/j.enbuild.2004.08.007
  30. Jiru and Haghighat (2008) Modeling ventilated double skin facade-A zonal approach (pp. 1567-1576) https://doi.org/10.1016/j.enbuild.2008.02.017
  31. Zhang, C., Wang, J., Xu, X., Kang, J.: Development of a simplified model of switchable exhaust air insulation window. ASHRAE/IBPSA-USA Building Simulation Conference, Atlanta (2014)
  32. Ismail and Henríquez (2005) Two-dimensional model for the double glass naturally airflow window (pp. 461-475) https://doi.org/10.1016/j.ijheatmasstransfer.2004.09.022
  33. Gloriant et al. (2015) Modeling a triple-glazed supply-air window (pp. 1-9) https://doi.org/10.1016/j.buildenv.2014.10.017
  34. Khalvati and Omidvar (2019) Summer study on thermal performance of an exhausting airflow window in evaporatively-cooled buildings (pp. 147-158) https://doi.org/10.1016/j.applthermaleng.2019.02.135
  35. International Standard Organization. Ergonomics of the thermal environment – Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. ISO Standard No.7730. Retrieved from
  36. https://www.iso.org/standard/39155.html
  37. (2005)
  38. Omidvar and Kim (2020) Modification of sweat evaporative heat loss in the PMV/PPD model to improve thermal comfort prediction in warm climates https://doi.org/10.1016/j.buildenv.2020.106868
  39. Shen et al. (2016) A study on thermoelectric technology application in net zero energy buildings (pp. 9-24) https://doi.org/10.1016/j.energy.2016.07.038
  40. Iranian National Building Regulations. Chapter 19: Energy-saving, (In Persian). Retrieved from
  41. http://inbr.ir/?page_id=2032
  42. (2010)
  43. British Standard. Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics. (BS EN 15251). Retrieved from
  44. http://www.cres.gr/greenbuilding/PDF/prend/set4/WI_31_Pre-FV_version_prEN_15251_Indoor_Environment.pdf
  45. (2007)