Published in Issue 2013-04-18
How to Cite
Acikkalp, E. (2013). Modified thermo-ecological optimization for refrigeration systems and an application for irreversible four-temperature-level absorption refrigerator. International Journal of Energy and Environmental Engineering, 4(1 (December 2013). https://doi.org/10.1186/2251-6832-4-20
HTML views: 54
PDF views: 123
Abstract
Abstract
In this study, a modified ecological function is presented for four-temperature-level absorption refrigerators, and an absorption refrigerator has been optimized using this function. An equivalent system was initially identified, followed by the application of the first and second laws of thermodynamics. Next, the optimization results were interpreted. The results of the optimization process, optimum point of
x
H
,
x
R
,
a
H
, and
a
R
,
were defined as 0.87, 0.58, 2.41, 0.25, respectively. In addition to that, the effects of
x
H
,
x
R
,
a
H
,
a
R
,
T
a
,
T
c
,
T
e
, and
T
g
were shown according to exergy destruction, ecological function, coefficient of performance, and cooling load. As a result, it was understood that especially the
x
H
, parameter, and the generator temperatures are the variables of the system that require special attention because, at some points, they cause that generator and absorber transfer heat in the opposite direction they need to do.
Keywords
- Absorption system,
- Optimization,
- Irreversibility,
- Refrigeration,
- Ecological
References
- Angulo-Brown (1991) An ecological optimization criterion for finite-time heat engines 69(11) (pp. 7465-7469) https://doi.org/10.1063/1.347562
- Yan (1993) Comment on “Ecological optimization criterion for finite-time heat-engines” 73(7) https://doi.org/10.1063/1.354041
- Bhardwaj et al. (2003) Finite time optimization of an endoreversible and irreversible vapour absorption refrigeration system 44(7) (pp. 1131-1144) https://doi.org/10.1016/S0196-8904(02)00101-2
- Bhardwaj et al. (2005) General performance characteristics of an irreversible vapour absorption refrigeration system using finite time thermodynamic approach 44(2) (pp. 189-196) https://doi.org/10.1016/j.ijthermalsci.2004.07.004
- Huang et al. (2008) Performance optimization for an irreversible four-temperature-level absorption heat pump 47(4) (pp. 7479-7485) https://doi.org/10.1016/j.ijthermalsci.2007.03.013
- Chen (1999) The optimum performance characteristics of a four-temperature-level irreversible absorption refrigerator at maximum specific cooling load 32(23) (pp. 3085-3910) https://doi.org/10.1088/0022-3727/32/23/315
- Chen (1997) Optimal performance analysis of irreversible cycles used as heat pumps and refrigerators 30(4) (pp. 582-587) https://doi.org/10.1088/0022-3727/30/4/012
- Sun et al. (2005) Optimization between heating load and entropy-production rate for endoreversible absorption heat-transformers 81(4) (pp. 434-448) https://doi.org/10.1016/j.apenergy.2004.09.003
- Chen et al. (2006) Irreversible four-temperature-level absorption refrigerator 80(3) (pp. 347-360) https://doi.org/10.1016/j.solener.2005.01.013
- Chen and Yan (1998) An ecological optimization criterion for a class of irreversible absorption heat transformers 31(9) (pp. 1078-1082) https://doi.org/10.1088/0022-3727/31/9/008
- Yan and Chen (1996) Optimization of the rate of exergy output for an endoreversible Carnot refrigerator 29(12) (pp. 3017-3021) https://doi.org/10.1088/0022-3727/29/12/013
- Yan and Lin (2000) Ecological optimization criterion for an irreversible three-heat-source refrigerator 66(3) (pp. 213-224) https://doi.org/10.1016/S0306-2619(99)00134-8
- Fathi et al. (2004) An irreversible thermodynamic model for solar absorption refrigerator 29(8) (pp. 1349-1365) https://doi.org/10.1016/j.renene.2003.07.011
- Gordon and Ng (2000) Cambridge International Science
- Ng et al. (1999) Thermodynamic modeling of absorption chiller and comparison with experiments 20(2) (pp. 42-51) https://doi.org/10.1080/014576399271574
- Ng and Wang (2005) Thermodynamic methods for performance analysis of chillers 219(2) (pp. 109-116) https://doi.org/10.1243/095440805X28249
- Gordon and Ng (1995) Predictive and diagnostic aspects of a universal thermodynamic models for chillers 38(5) (pp. 807-818) https://doi.org/10.1016/0017-9310(94)00208-D
- Morosuk et al. (2012) Advanced exergy-based analyses applied to a system including LNG regasification and electricity generation 3(1) (pp. 1-9) https://doi.org/10.1186/2251-6832-3-1
- Tsatsaronis and Morosuk (2010) Advanced exergetic analysis of a refrigeration system for liquefaction of natural gas 1(1) (pp. 1-17)
- Palazzo (2012) Thermal and mechanical aspect of entropy-exergy relationship 3(4) (pp. 1-10)
- Chen et al. (2007) Exergy-based ecological optimization for a generalized irreversible Carnot heat-pump 84(1) (pp. 78-88) https://doi.org/10.1016/j.apenergy.2006.04.003
- Florides et al. (2003) Design and construction of a LiBr–water absorption machine 44(15) (pp. 2483-2508) https://doi.org/10.1016/S0196-8904(03)00006-2
10.1186/2251-6832-4-20